Udaş Uşak Doğal Gaz Dağıtım A.Ş.. Provinces served: Uşak. Rules: read from the company code

Calculation rules

Service box → meter loss limit1 mbar
Meter → appliance loss limit0.8 mbar
Velocity limit (low pressure)6 m/s
Friction loss, steeltable for Q ≤ 31 m³/h, formula above
Efficiency in appliance flow90% at 70 kW and above
Isometric angle30°

Code source

UDAŞ Doğal Gaz İç Tesisat Şartnamesi, s. 48–51

How to select it in GazPlan

Open the app and choose Uşak as the province in the wizard or project panel; Udaş Uşak Doğal Gaz Dağıtım A.Ş. is selected and the calculation uses these rules. Open the app

For information only; the distribution company's current code applies to projects.