Udaş Uşak Gas Project Rules
Udaş Uşak Doğal Gaz Dağıtım A.Ş.. Provinces served: Uşak. Rules: read from the company code
Calculation rules
| Service box → meter loss limit | 1 mbar |
|---|---|
| Meter → appliance loss limit | 0.8 mbar |
| Velocity limit (low pressure) | 6 m/s |
| Friction loss, steel | table for Q ≤ 31 m³/h, formula above |
| Efficiency in appliance flow | 90% at 70 kW and above |
| Isometric angle | 30° |
Code source
UDAŞ Doğal Gaz İç Tesisat Şartnamesi, s. 48–51
How to select it in GazPlan
Open the app and choose Uşak as the province in the wizard or project panel; Udaş Uşak Doğal Gaz Dağıtım A.Ş. is selected and the calculation uses these rules. Open the app
For information only; the distribution company's current code applies to projects.